Wire the controller, Terminal block layouts – Rockwell Automation 1766-L32xxx MicroLogix 1400 Programmable Controllers Installation Instructions User Manual

Page 19

Advertising
background image

MicroLogix 1400 Programmable Controllers 19

Publication 1766-IN001C-EN-P - October 2009

3. Replace the cover as shown below.

The MicroLogix 1400 controller is designed to support up to any seven 1762 expansion I/O
modules.

For detailed information on using expansion I/O, refer to the installation instructions for
your expansion module.

Wire the Controller

The shading in the following terminal block illustrations indicates which terminal groups are
tied to which commons.

Terminal Block Layouts

WARNING

When you connect or disconnect the Removable Terminal Block (RTB) with field
side power applied, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.

WARNING

When used in a Class I, Division 2, hazardous location, this equipment must be
mounted in a suitable enclosure. All wiring must be in accordance with Class I,
Division 2 wiring methods of Article 501 of the National Electrical Code and/or
in accordance with Section 18-1J2 of the Canadian Electrical Code, and in
accordance with the authority having jurisdiction.

44523

Advertising