Rockwell Automation 1766-L32xxx MicroLogix 1400 Programmable Controllers Installation Instructions User Manual

Page 35

Advertising
background image

MicroLogix 1400 Programmable Controllers 35

Publication 1766-IN001C-EN-P - October 2009

Certifications for 1766-L32AWA, 1766-L32AWAA, 1766-L32BWA,

1766-L32BWAA, 1766-L32BXB, 1766-L32BXBA

Surge transient
immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on AC power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±1 kV line-earth(CM) on communications ports

Conducted RF immunity IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Voltage variation

IEC 6100-4-11:
60% dip for 10 periods on AC supply ports
30% dips for 25 periods @ 0

° and 180° on AC supply ports

100% dip for 250 periods @ 0

° and 180° on AC supply ports

100% dip for 0.5 periods, arbitrary angle, on AC supply ports

Certification (when
product is marked)

(1)

(1)

See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates, and other certification

details.

Value

UL

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations.

See UL File E10314.

c-UL

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for

Canada. See UL File E10314.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

Description

1766-L32AWA
1766-L32AWAA

1766-L32BWA
1766-L32BWAA

1766-L32BXB
1766-L32BXBA

Advertising