30 MicroLogix 1400 Programmable Controllers
Publication 1766-IN001C-EN-P - October 2009
Analog Outputs
Description
1766-L32AWAA, -L32BWAA, -L32BXBA
Number of inputs
2 single-ended
Voltage output range
0…10 V DC - 1 LSB
Type of data
12 bit unsigned integer
Step response
2.5 ms @ 95%
Load range
Voltage output
1 K
Ω
Output resolution
12 bit
Analog output setting time
3 ms (max.)
Overall Accuracy
-20…60 °C (-4…140 °F)
±
1.0% of full scale
Electrical isolation
Non-isolated with internal logic
Cable length
30 m (98 ft) shielded cable
Relay and FET Outputs
Description
1766-L32AWA, 1766-L32AWAA,
1766-L32BWA, 1766-L32BWAA
1766-L32BXB,
1766-L32BXBA
Maximum controlled load
1440 VA
1080 VA
Maximum Continuous Current:
Current per channel and group common 2.5 A per channel
8A max channel 8…11 common
2.5 A per channel
Current per controller
at 150V max
28 A or total of per-point loads,
whichever is less
at 240V max
20 A or total of per-point loads,
whichever is less
Relay Outputs
Description
1766-L32AWA, 1766-L32AWAA, 1766-L32BWA,
1766-L32BWAA, 1766-L32BXB, 1766-L32BXBA
Turn On Time/Turn Off Time
10 ms (maximum)
(1)
Load current
10 mA (minimum)
(1)
Scan time dependent