Working Voltage

Turn-On Time (maximum)

11

µs

28 ns

Turn-Off Time (maximum)

89

µs

2.3

µs

(1)

Output 2, 3 and 4 are designed to provide increased functionality over the other FET outputs. Output 2, 3 and 4 may be used

like the other FET transistor outputs, but in addition, within a limited current range, they may be operated at a higher speed.

Output 2, 3 and 4 also provide a pulse train output (PTO) or pulse width modulation output (PWM) function.

Working Voltage for 1766-L32AWA, 1766-L32AWAA

Description

Recommendation

Power supply input to
backplane isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or
2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Input group to backplane
isolation

Verified by one of the following dielectric tests:1517V AC for 1 second or
2145V DC for 1 second

132V AC Working Voltage (IEC Class 2 reinforced insulation)

Input group to input group
isolation

Verified by one of the following dielectric tests:1517V AC for 1 second or
2145V DC for 1 second

132V AC Working Voltage (basic insulation)

Output group to backplane
isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or
2596V DC for 1 second

265V AC Working Voltage (IEC Class 2 reinforced insulation)

Output group to output
group isolation

Verified by one of the following dielectric tests: 1836V AC for 1 second or
2596V DC for 1second

265V AC Working Voltage (basic insulation), 150V AC Working Voltage (IEC
Class 2 reinforced insulation)