Span Your Clamp and Ejector Valves

Chapter 9

9-16

Test Your Clamp Close Velocity Valve(s) for Linearity

1.

Select velocity vs. position control for the entire Clamp Close
operation by resetting (= 0) the following three bits:

CPC03-B00 (Pro-Set 600 address B37/288)
CPC03-B02 (Pro-Set 600 address B37/290)
CPC03-B04 (Pro-Set 600 address B37/292)

2.

Select velocity setpoints for Clamp Close that are typical of the
velocities you would run during normal machine operation. Enter
these setpoints into CPC09, CPC12, and CPC15 (Pro-Set 600
addresses N43:245, N43:248, and N43:251).

3.

Download changes to the QDC module (refer to chapter 4 for detailed
instructions).

4.

Jog your clamp to the full open position.

5.

Enable First Clamp Close (DYC02-B00, Pro-Set 600 address
B35/400). The clamp should move from its start position through the
First Clamp Close profile, and then execute Low Pressure Close. If
no motion is observed, check the following:

- Verify that none of your clamp or ejector overtravel alarms are set.

The QDC module inhibits clamp close if SYS07-B00 through
SYS07-B05 are set

- Verify that the ejector is inside the ejector position for clamp close

enable (EPC63)

- Verify that no programming error codes exist in SYS61 and

SYS62

6.

Upon completion of Clamp Close, observe the velocity reported back
for 1st clamp close segment 2 (CPS12, Pro-Set 600 address
N43:664). This velocity should be relatively close to the setpoint you
entered in CPC12 (Pro-Set 600 address N43:248). If the observed
velocity is not within 25% of the setpoint:

- Verify you chose the correct values from your flow rate curves

supplied by your flow valve manufacturer

- Verify your calculations