Ground and shield your i/o devices – Rockwell Automation 1771-QDC, D17716.5.87(Passport) CLAMP AND EJECT MODE User Manual

Page 30

Advertising
background image

Install the QDC Module

Chapter 2

2-9

Analog inputs and outputs are sensitive to electrical noise interference.
Take care to shield them properly.

Guidelines:

Use 22-gage (or larger) twisted-pair cable, 100% shielded with drain

wire, such as Belden 8761 (or equivalent). For cable distances over
50 ft, use 18-gage cable such as Belden 8760 (or equivalent)

Ground the cable shield at one end only; generally at the sensor or

amplifier end, not at the I/O chassis (see Figure 2.4 and Figure 2.5)

Figure 2.4

Shielding Differential Inputs

Connect the cable shield

and case ground to earth

ground at the Input Sensor

Input Sensor

18

17

14

QDC Module Input

Input Module Common

should float

+

10910Ć2

+15V

-15V

No User Connections.

For Test Purposes, Only.

Ground and Shield

Your I/O Devices