ControlNet Foundation Fieldbus Linking Device 15

Publication

1757-IN022B-EN-P - August 2009

H1 Terminal Block

The linking device provides two parallel terminals on each H1 network. Use
one to connect to your fieldbus devices and the other for short-term
connection of diagnostic devices.

Do these steps to connect the H1 cables.

1. Strip about 5…7 mm (0.2…0.28 in.) of the insulation at the ends of

the cable leads.

2. Insert the stripped cable end into the desired RTB, and tighten the

screw to 0.34 N•m (3 lb•in).

3. Complete

step 1

and

step 2

for all H1 cables.

4. If you removed the RTB to insert the H1 cables, insert the RTB into

the corresponding socket and tighten the retaining screws.

WARNING

When you connect or disconnect the removable terminal block (RTB) with field
side power applied, an electrical arc can occur. This could cause an explosion
in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

ATTENTION

Be careful when stripping wires. Wire fragments that fall into the linking
device could cause damage.

IMPORTANT

The H1 RTBs are keyed so they fit only into the corresponding socket. Be
certain that you connect the cables to the correct RTBs.

You must use a power conditioner between your fieldbus power supply and
the devices on the fieldbus network. For more information, see the
F

OUNDATION

Fieldbus Wiring and Installation Application Guide at

http://www.fieldbus.org,

publication

AG-140

.