24 ControlNet Foundation Fieldbus Linking Device

Publication

1757-IN022B-EN-P - August 2009

ControlNet Channel Troubleshooting (A OR B)

OR

Cause

Action

Off

Channel disabled

Use RSNetWorx for ControlNet software to
configure the ControlNet network for
redundant media, if required.

Solid green

Normal operation

None.

Flashing
green/off

Temporary network errors

Check media for broken cables, loose
connectors, or missing terminators.

If condition persists, refer to the
ControlNet Media Planning and
Installation Manual, publication

CNET-IN002.

Flashing
red/off

Media fault

Check media for broken cables, loose
connectors, or missing terminators.

If condition persists, refer to the
ControlNet Media Planning and
Installation Manual, publication

CNET-IN002.

No other nodes present
on network

Add other nodes to the network.

Flashing
red/green

Incorrect ControlNet node
address greater than
UMAX

Change linking device node address
so that it is less than or equal to

UMAX

(1)

.

Cycle power to the linking device

Incorrect network
configuration

Use RSNetWorx for ControlNet software to
reconfigure the ControlNet network so that

UMAX

(1)

is greater than or equal to the

linking device’s node address.

(1)

UMAX is the highest node address on a ControlNet network that can transmit data.