Before you begin – Rockwell Automation 1757-FFLDC4 ControlNet Foundation Fieldbus Linking Device Installation Instructions User Manual

Page 7

Advertising
background image

ControlNet Foundation Fieldbus Linking Device 7

Publication

1757-IN022B-EN-P - August 2009

Before You Begin

Before you install the linking device, read and complete the following
sections.

Software Requirements

The following software is compatible with this revision of the linking device:

• RSFieldbus software, version 2.03 or later
• RSLinx Classic software, version 2.52 or later
• RSNetWorx for ControlNet software, version 8.00 or later
• Logix5000 Clock Update tool
• RSLogix 5000 programming software, version 16.03 or later

WARNING

This product contains a ControlNet daughtercard (CAM) that is not intended for
removal. Any attempt to remove this CAM or to operate the CAM release
mechanism may cause irreparable damage. If you insert or remove the CAM
while host power is on, an electrical arc can occur. This could cause an
explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

IMPORTANT

You must upgrade your linking device to RSLogix 5000 programming
software version 17 to program unscheduled Class 1 connections on the
ControlNet network. The upgrade is required if your system is running
RSLogix 5000 software version 16 without redundancy. If you are using
RSLogix 5000 software version 16 with redundancy, unscheduled Class 1
connections are not available on the ControlNet network.

Advertising