ControlNet Status Indicators

IMPORTANT

When you connect the module to a ControlNet network by using only
the network access port (NAP), the status indicators are not accurate.

ControlNet Network Troubleshooting (A AND B)

AND

Cause

Action

Off

No power

None or apply power to the linking device.

Faulted ControlNet
interface

Cycle power to the linking device.

If fault persists, contact your Rockwell
Automation Technical Support
representative or distributor.

Invalid node address of 00

Choose a valid node address.

Cycle power to the linking device.

Solid red

Faulted ControlNet
interface

Cycle power to the linking device.

If fault persists, contact your Rockwell
Automation Technical Support
representative or distributor.

Alternating
red/green

Self-test

None.

Incorrect channel
configuration

Verify that the ControlNet network is
connected to the correct channel of the linking
device (for example, if the ControlNet network
is configured for channel A only, then the
linking device must be connected to the
network via channel A).

Alternating
red/off

Duplicate ControlNet node
address

Choose a unique node address.

Cycle power to the linking device.