Rockwell Automation 1757-FFLDC4 ControlNet Foundation Fieldbus Linking Device Installation Instructions User Manual

Page 26

Advertising
background image

26 ControlNet Foundation Fieldbus Linking Device

Publication

1757-IN022B-EN-P - August 2009

Wire size

DC power connection

Fieldbus connections

Ethernet connections

0.2... 1.5 mm

2

(26...16 AWG) solid or

stranded copper wire rated at 75 °C (167 °F)
or greater 1.2 mm (3/64 in.) insulation max

0.8 mm

2

(18 AWG) solid or stranded shielded

twisted pair copper wire rated at 75 °C
(167 °F) or greater 1.2 mm (3/64 in.)
insulation max

RJ45 connector according to IEC 60603-7,
2 or 4 pair Category 5e min cable according
to TIA 568-B.1 or Category 5 cable according
to ISO/IEC 24702

Program retention (unpowered)

21 days

In-circuit battery life

5000 charge/discharge cycles (about 13
years)
Battery is not replaceable

North American temp code

T4

IEC temp code

T4

Enclosure type rating

None (open-style)

(1)

Each network defined as a F

OUNDATION

Fieldbus 31.25 Kbps H1 network.

(2)

Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

1757-FFLDC2, 1757-FFLDC4 - Technical Specifications

Attribute

Value

Advertising