22 ControlNet Foundation Fieldbus Linking Device

Publication

1757-IN022B-EN-P - August 2009

BATT
(battery)

Off

Normal operation.

Flashing red

Jumper is missing (or not seated on the two rightmost pins), or

the battery is low or dead.

(1)

NS
(network
status)

Off

Not powered.

Flashing green No connections to the Logix blocks in the controller or to the

Logix blocks in the linking device.

Verify physical connection by using the ControlNet
status indicators.

Verify that:

the Logix block is downloaded to the controller (via

RSLogix 5000 software) and the linking device (via
RSFieldbus software).

the Logix blocks’ slot numbers correspond in

RSLogix 5000 software and RSFieldbus software.

the ControlNet network has been scheduled at least

once when using unscheduled connections to Logix
blocks and all Logix blocks using scheduled
connections have been scheduled.

Solid green

CIP Class 1 connections.

Flashing red

Connection timeout.
Verify that the linking device is connected to the ControlNet
network.

Solid red

Duplicate ControlNet node address.

Flashing red
and green

Self test.

MODE

Solid green

Linking device operational.

Flashing green Linking device out-of-service.

Verify that the Resource Block is set to Target Auto mode.

(1)

If the BATT status indicator remains on after the jumper is replaced, and power has been returned to
the linking device, contact Rockwell Automation Technical Support.

Module Status Indicators

Indicator

Status

Description