ControlNet Foundation Fieldbus Linking Device 21

Publication

1757-IN022B-EN-P - August 2009

Status Indicators

Use the information in the following table to interpret the status indicators.

Module Status Indicators

Indicator

Status

Description

H1

Off

The H1 channel is inactive.
Verify that the linking device is connected to the H1 network.

Flashing green The linking device H1 channel is active.

STATUS
(module)

Off

No power - Module does not have 24V DC power.

Flashing green Standby - Module not configured.

Solid green

Operational - Module operating correctly.

Flashing red

Minor fault - A recoverable fault has been detected.
Verify that the configuration is correct and consistent.

Solid red

Major fault - An unrecoverable fault has been detected.
Recycle power to the module. If this does not clear the fault,
replace the module.

WDOG
(watchdog)

Off

Normal operation.

Flashing red

Software fault.
Contact Rockwell Automation Technical Support.