28 ControlNet Foundation Fieldbus Linking Device

Publication

1757-IN022B-EN-P - August 2009

EFT/B immunity

IEC 61000-4-4

±2 kV at 5 kHz on shielded fieldbus ports
±2 kV at 5 kHz on ControlNet ports

Surge transient immunity

IEC 61000-4-5

±2 kV line-earth (CM) on shielded fieldbus
ports
±2 kV line-earth (CM) on ControlNet ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz on ControlNet and
shielded fieldbus ports

Magnetic field immunity

IEC 61000-4-8

30 A/m long duration at 50 Hz

1757-FFLDC2, 1757-FFLDC4 - Certifications

(1)

Certification

(2)

Value

c-UL-us

UL Listed for Class I, Division 2 Group
A,B,C,D Hazardous Locations, certified for
U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC

Directive, compliant with:

EN 61326-1; Meas./Control/Lab.,
Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable
Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act,
compliant with:

AS/NZS CISPR 11; Industrial
Emissions