Specifications – Rockwell Automation 1757-FFLDC4 ControlNet Foundation Fieldbus Linking Device Installation Instructions User Manual

Page 25

Advertising
background image

ControlNet Foundation Fieldbus Linking Device 25

Publication

1757-IN022B-EN-P - August 2009

Specifications

1757-FFLDC2, 1757-FFLDC4 - Technical Specifications

Attribute

Value

Physical interfaces

2 or 4 H1 F

OUNDATION

Fieldbus interfaces

1 redundant media ControlNet interface

Number of H1 networks

(1)

per linking device

2 for 1757-FFLDC2 linking device, 4 for
1757-FFLDC4 linking device

Number of fieldbus devices
per H1 network, max

16 (8…10 recommended)

Number of fieldbus devices
per linking device, max

32 for the 1757-FFLDC2 linking device
64 for the 1757-FFLDC4 linking device

Power requirements

Current rating/supply power
In rush current
Power consumption/dissipation

450 mA @ 24V DC (± 10%)
1.5 A
9.6 W

Isolation voltage

50V (continuous), Basic Insulation Type,
Fieldbus to system backplane, Ethernet
network to system backplane, ControlNet
network to system backplane, and
ControlNet Channel A to ControlNet Channel
B

Type tested at 500V AC for 60 s

Panel mounting screw torque
(using M4 or #8 screws)

1.1…1.8 N•m (10…16 lb•in)

Wiring category

(2)

2 - on Fieldbus ports

3 - on power and Ethernet ports

2 - on ControlNet ports

Terminal block torque specifications

0.34 N•m (3 lb•in) on power and Fieldbus
wire connections