Installing the KF3

Chapter 2

2Ć3

Table 2.A

Wire/Terminal Connections for Imtermediate Nodes

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

NonĆjacketed

Terminal 2 - Shield

Black/White

Black Wire
White Wire

Cut back - No connection
Terminal 3 (Signal Ground)

Black/Red

Black Wire
Red Wire

Terminal 4 (Data A)
Terminal 5 (Data B)

The nodes at each end of the network must be terminated. Install a jumper
wire between terminals 5 and 6 to enable the impedance built into the
module.

One (not both) of the nodes at the end of the network must have an earth
ground connection for the communication cable shield. For the node
at one end of the network, whether it is the KF3 or some other device,
connect the shield to ground by installing a jumper wire between terminals
1 and 2 of the terminal block.

CAUTION: Be sure no other node on the network has its shield
connected to ground.

Figure 2.3 illustrates proper jumper connections for end nodes.

Figure 2.3

Jumper Connections for End Nodes

Jumper to

ground shield

KF3 on one end of the link

Jumper to

terminate node

SLC 500 or other device on the other

end of the link

Jumper to

terminate node

* The black wire of the white/black pair should be cut back (no connection).