Installing the dhć485 cable – Rockwell Automation 1770-KF3 DH-485 Communication Interface User Manual User Manual

Page 15

Advertising
background image

Installing the KF3

Chapter 2

2Ć7

Figure 2.9

Connection for Last Segment of a Multidrop Network

Third node

Jumper to

terminate node

Fourth node on the end of the multidrop network

* The black wire of the white/black pair should be cut back (no connection).

DHĆ485

Cable

Installing the DHĆ485 Cable

The DH-485 cable consists of a number of daisy-chained segments. The
total length of the combined segments must not exceed 4,000 feet. Cut the
cable segments long enough to route from one node to the next, allowing
sufficient slack to prevent strain on the connectors. Provide strain relief
for the cable after it is plugged in to prevent the cable wires from breaking.

Figure 2.10

Cable Connection on a DHĆ485 Link

ЛЛ

ЛЛ

BELDEN

#9842

BELDEN

#9842

Connector

(Phoenix MSTBĆ2.5/6ĆSTĆAU)

KF3

Link

Coupler

1747ĆAIC

Link

Coupler

1747ĆAIC