Configuring the KF3

Chapter 3

3Ć2

Displays

Figure 3.1 shows the configuration displays on the bottom of the module.
The left display (one digit) shows the number of the communication
parameter being configured. The right display (two digits) shows the
current setting for that parameter. Communication parameters are
configured in two menus, a main menu, for basic parameters, and a
submenu, for more advanced parameters.

Push Buttons

Figure 3.1 shows three push buttons labelled View, Data, and Exit. The
operation of these buttons is described in Table 3.A.

Table 3.A

Push Button Operation

Pressing this button or

button combination:

Performs this task:

View

In run mode, takes the module into configuration mode.
Note: This is the only button that has a function in run mode.
In configuration mode, cycles through the possible

communication parameters (displayed on the left digit).
If you hold the button down for more than 1 second, the

parameter numbers will advance automatically.

Data

In configuration mode, cycles through the possible

communication parameters for the parameter shown on the left.

The data is displayed on the right two digits. If you hold the

button down for more than 1 second, the parameter numbers will

advance automatically.

Exit

In configuration mode, from the main menu, returns the module

to run mode without saving any changes. The change in mode

takes effect when the button is released.
From the submenu, returns to the main menu without saving any

changes.

View + Exit

In configuration mode, saves all configuration changes, and

returns the module to run mode from either menu. The module

will begin operating with the new configuration as soon as it

returns to run mode.

View + Data

In configuration mode, resets all communication parameters

to their factory defaults (see Table 3.B). The changes do not

take effect until the configuration is saved, and the module

returns to run modeĊthat is, until View and Exit are pushed

simultaneously.