5 - troubleshooting the kf3, Interpreting the front panel leds, Troubleshooting the kf3 – Rockwell Automation 1770-KF3 DH-485 Communication Interface User Manual User Manual

Page 44

Advertising
background image

Chapter

5

5Ć1

Troubleshooting the KF3

There are four LEDs on the front panel of the KF3. These indicators
can help you in diagnosing problems with the module’s installation and
operation.

Table 5.A

LED Indicators

LED Indicator

Description

Power

This indicator is lit (green) when the module is plugged in and turned on.

Fault

This indicator goes on solid red if a hardware fault is detected on power

up, or during operation. If this occurs, the type of fault is displayed on the

left numeric display on the bottom of the module. Refer to the section on

Interpreting the Numeric Displays" on page 5Ć2 for information on fault

codes.
This indicator will flash red at 1Ćsecond intervals when a station with

the same address as this node is detected. To correct the fault, go into

configuration mode and change the address of one of the stations to an

unused one.

RSĆ232C Activity

This indicator flickers green when data is received by the module from

the host computer. The more activity on the RSĆ232C link, the faster this

indicator will flash. At times of high activity, the indicator may flash so

rapidly that it appears to be solid green.

DHĆ485 Activity

Shows activity on the DHĆ485 network. It turns on (green) while the KF3

has the token, and turns off when another station on the network has

the token. It will flash slower as more stations are added to the network,

since this node will have the token less frequently. It will also slow down

if other nodes on the network are transmitting large data packets.

Interpreting the Front Panel
LEDs

Advertising