Rockwell Automation 1770-KF3 DH-485 Communication Interface User Manual User Manual

Page 12

Advertising
background image

Installing the KF3

Chapter 2

2Ć4

Connecting via a DHĆ485 Link (PointĆtoĆPoint Configuration)

Figure 2.4 shows a point-to-point link consisting of a single SLC 500
programmable controller and one host computer station.

Figure 2.4

A PointĆtoĆPoint DHĆ485 Link

DHĆ485 Cable

Belden #9842

RSĆ232C

Cable

Host Computer

KF3

1747ĆC11 Cable

SLC 500

Controller

Link

Coupler

1747ĆAIC

This configuration requires a KF3 and one link coupler. The SLC 500
controller is connected to the link coupler with a 1747-C11 cable. The
KF3 is connected directly to the link coupler. In this topology, both the
KF3 and the SLC 500 are end nodes.

Construct a cable to attach the DH-485 connector on the back of the
KF3 module to the link coupler. Figure 2.5 shows the connection for a
point-to-point DH-485 application. The shield ground could be at either
end, but must be at one end, and one end only.

Figure 2.5

Connection for KF3 and Single SLC

Jumper to ground

shield connector

KF3 on one end of the link

Jumper to

terminate node

SLC 500 or other device at the other end of the link

Jumper to

terminate node

* The black wire of the white/black pair should be cut back (no connection).