Installing your remote i/o adapter module – Rockwell Automation 1794-ASB/E Remote I/O Adapter Module User Manual User Manual

Page 19

Advertising
background image

Chapter

2

Publication 1794ĆUM009D-EN-P - April 2004

Installing Your Remote I/O

Adapter Module

This chapter describes the procedures for installing your remote I/O
adapter module. These include:

power requirements

mounting the remote I/O adapter

setting the module switches

ATTENTION

!

Environment and Enclosure

This equipment is intended for use in a Pollution
Degree 2 industrial environment, in overvoltage
Category II applications (as defined in IEC
publication 60664–1), at altitudes up to 2000
meters without derating.

This equipment is considered Group 1, Class A
industrial equipment according to IEC/CISPR
Publication 11. Without appropriate precautions,
there may be potential difficulties ensuring
electromagnetic compatibility in other
environments due to conducted as well as radiated
disturbance.

This equipment is supplied as “open type”
equipment. It must be mounted within an
enclosure that is suitably designed for those
specific environmental conditions that will be
present, and appropriately designed to prevent
personal injury resulting from accessibility to live
parts. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent
sections of this publication may contain additional
information regarding specific enclosure type
ratings that are required to comply with certain
product safety certifications.

See NEMA Standards publication 250 and IEC
publication 60529, as applicable, for explanations
of the degrees of protection provided by different
types of enclosures. Also, see the appropriate
sections in this publication, as well as the
Allen–Bradley publication 1770–4.1, (“Industrial
Automation Wiring and Grounding Guidelines”),
for additional installation requirements pertaining
to this equipment.

Chapter Objectives