Rockwell Automation 1794-ASB/E Remote I/O Adapter Module User Manual User Manual
Page 29

FlipĆopen
cover
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
ON
ON
S1
S2
Starting
I/O Group
I/O Rack
Number
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
ON
ON
S1
S2
Hold Last State
Processor Restart Lockout
Communication Rate/Mode switches 3 and 4
Rack Fault
Hold Inputs
Mode Switch 0
Mode Switch 1
Mode
Switch 2
Mode Switch 4
Mode Switch 3
2–11
Installing Your Remote I/O Adapter Module
Publication 1794ĆUM009D-EN-P - April 2004
Starting I/O Group
1
S1-8
S1-7
I/O group
ON
ON
0 (1st quarter)
OFF
ON
2 (2nd quarter)
ON
OFF
4 (3rd quarter)
OFF
OFF
6 (4th quarter)
1 In 32 point mode, starting quarter must be 0
(S1-8 and S1-7 on).
I/O Rack Number
S1-6 thru S1-1
Refer to page 2-13
S2-8
Mode Switch 0
Refer to Mode Selection Switches, 2-12
S2-7
HoldInputs
ON
Hold Inputs
OFF
Reset Inputs
S2-6
Rack Fault
ON
Not Enabled (default)
OFF
Enabled
S2-5
Mode Switch 1
Refer to Mode Selection Switches, 2-12
Communication Rate/
32-pt Mode Select
S2-4 S2-3
Bits/s
ON
ON
57.6k
OFF
ON
115.2k
ON
OFF
230.4k
OFF
OFF
Autobaud (use only with 32Ćpt
mode
1
) Use these switches to put
the adapter in 32-pt mode and
perform autobaud.
1
Cycle power to the 1794ĆASB/E or push the reset
button when baud rate is changed in the scanner.
Processor Restart Lockout (PRL)
S2-2
Processor:
ON
Restart
OFF
Locked out
HoldLast State (HLS)
S2-1
Processor will:
ON
Reset outputs
OFF
Hold last state