2–12

Installing Your Remote I/O Adapter Module

Publication 1794ĆUM009D-EN-P - April 2004

Set the mode selection switches for the desired mode as follows.

1. Lift the hinged switch cover on the front of the adapter to expose

the switches.

2. Set the switches as shown below.

3. Cycle power to the adapter to activate the settings.

When Using this

Addressing Mode

And

Mode Switch 2

S1Ć1

Mode Switch 1

S2Ć5

Mode Switch 0

S2Ć8

Standard

1

8 and/or 16Ć point

modules

See note 1

ON

ON

Compact

2

8Ćpoint modules

OFF

ON

OFF

16Ćpoint modules

ON

ON

OFF

Complementary

See Complementary Rack Addressing Table, page2-15

Primary chassis

8Ćpoint modules

OFF

OFF

ON

Complementary chassis

8Ćpoint modules

ON

OFF

ON

Complementary

See Complementary Rack Addressing Table, page 2-15

Primary chassis

16Ćpoint modules

2

OFF

OFF

OFF

Complementary chassis

16Ćpoint modules

2

ON

OFF

OFF

1

In standard mode, this switch retains its function as switch position 1 of rack addressing. In Standard mode, the module is functionally

interchangeable with a 1794ĆASB series A or B adapter.

2

In compact mode, 32-point modules appear as 8 or 16-point modules.

3

When programming block transfers, address analog modules as module 0 if switch S1Ć1 is on; module 1 if switch S1Ć1 is off.

When Using this

Addressing Mode

And

Mode Switch 0

S2-8

Mode Switch 1

S2Ć5

Mode Switch 2

S1-1

Mode Switch 3

S2-3

Mode Switch 4

S2Ć4

Standard - 32

1

8, 16 and/or 32Ć

point modules

ON

ON

See note 1

OFF

OFF

Complementary - 32

Primary chassis

2

8, 16 and/or 32Ć

OFF

OFF

OFF

OFF

OFF

Complementary - 32

Complementary chassis

2

point modules

OFF

OFF

ON

OFF

OFF

1

In Standard - 32 mode, any module in the chassis occupies 32 input points and 32 output points in the Input/Output data table.

2

In Complementary - 32 mode, any module in the chassis occupies 32 input points or 32 output points in the Input/Output data table. If using an 8 point or 16 point module, the unused

points in the data table are zeroed out.

Setting the Mode Selection