3–3

Communicating with FLEX I/O Modules

Publication 1794ĆUM009D-EN-P - April 2004

Complementary

•

you don't need full FLEX I/O module

functionality, including combination

modules (1794ĆIB10XOB6), settable

input delay times on input modules

(1794ĆIB16, ĆIB8S), and fuse blown

indication (1794ĆOB8EP), for

example.

•

you can locate equal numbers of

input and output modules in

separate chassis

•

Eight 8 point modules in each chassis

equal 1/2 logical rack (when input

modules are installed in 1 chassis, and

output modules are installed in the

complementary chassis).

•

Eight 16 point modules in each chassis

equal 1 logical rack (when input modules

are installed in 1 chassis, and output

modules are installed in the

complementary chassis).

•

Provides maximum use of I/O image table

in 2 FLEX chassis (when input modules

are installed in 1 chassis, and output

modules are installed in the

complementary chassis).

•

You must configure all modules

in both chassis as either 8Ćpoint

or 16Ćpoint.

•

No combination modules

allowed

•

Configuration/status data is not

accessible to user

Standard - 32

•

you need full FLEX I/O module

functionality, including 32 point

modules, combination modules

(1794ĆIB10XOB6), settable input

delay times on input modules

(1794ĆIB16, ĆIB8S), and fuse blown

indication (1794ĆOB8EP) for

example.

•

User has access to 2 words of input, 2

words of output for each digital module.

•

Four modules equal 1 logical rack.

•

No restrictions on module placement

•

Maximum use of configuration/status and

combination modules

•

Inefficient I/O image table

utilization

Complementary - 32

•

you don't need full FLEX I/O module

functionality, including combination

modules (1794ĆIB10XOB6), settable

input delay times on input modules

(1794ĆIB16, ĆIB8S), and fuse blown

indication (1794ĆOB8EP), for

example.

•

you can locate equal numbers of

input and output modules in

separate chassis

•

Eight modules in each chassis equal 2

logical racks

•

Provides maximum use of I/O image table

in 2 FLEX chassis (when input modules

are installed in 1 chassis, and output

modules are installed in the

complementary chassis).

•

All digital I/O modules are

configured as 32Ćpoint.

•

No combination modules

allowed

•

Configuration/status data may

not be accessible to user

(depending on module type).

The amount of data accessible to the processor in the 5 addressing
modes is illustrated below. Note that the shaded areas represent data
not accessible by the processor.