Rockwell Automation 1794-ASB/E Remote I/O Adapter Module User Manual User Manual

Page 32

Advertising
background image

2–14

Installing Your Remote I/O Adapter Module

Publication 1794ĆUM009D-EN-P - April 2004

S1 Switch Position

Rack Number

1

2

3

4

5

6

PLCĆ3

PLCĆ5/250

PLCĆ5

1747ĆSN

Rack 42

ON

OFF

ON

ON

ON

OFF

Rack 43

OFF

OFF

ON

ON

ON

OFF

Rack 44

ON

ON

OFF

ON

ON

OFF

Rack 45

OFF

ON

OFF

ON

ON

OFF

Rack 46

ON

OFF

OFF

ON

ON

OFF

Rack 47

OFF

OFF

OFF

ON

ON

OFF

Rack 50

ON

ON

ON

OFF

ON

OFF

Rack 51

OFF

ON

ON

OFF

ON

OFF

Rack 52

ON

OFF

ON

OFF

ON

OFF

Rack 53

OFF

OFF

ON

OFF

ON

OFF

Rack 54

ON

ON

OFF

OFF

ON

OFF

Rack 55

OFF

ON

OFF

OFF

ON

OFF

Rack 56

ON

OFF

OFF

OFF

ON

OFF

Rack 57

OFF

OFF

OFF

OFF

ON

OFF

Rack 60

ON

ON

ON

ON

OFF

OFF

Rack 61

OFF

ON

ON

ON

OFF

OFF

Rack 62

ON

OFF

ON

ON

OFF

OFF

Rack 63

OFF

OFF

ON

ON

OFF

OFF

Rack 64

ON

ON

OFF

ON

OFF

OFF

Rack 65

OFF

ON

OFF

ON

OFF

OFF

Rack 66

ON

OFF

OFF

ON

OFF

OFF

Rack 67

OFF

OFF

OFF

ON

OFF

OFF

Rack 70

ON

ON

ON

OFF

OFF

OFF

Rack 71

OFF

ON

ON

OFF

OFF

OFF

Rack 72

ON

OFF

ON

OFF

OFF

OFF

Rack 73

OFF

OFF

ON

OFF

OFF

OFF

Rack 74

ON

ON

OFF

OFF

OFF

OFF

Rack 75

OFF

ON

OFF

OFF

OFF

OFF

Rack 76

ON

OFF

OFF

OFF

OFF

OFF

Not Valid

OFF

OFF

OFF

OFF

OFF

OFF

Rack address 77 is an illegal configuration.

PLCĆ5/11 processors can scan rack 03.

PLCĆ5/15 and PLCĆ5/20 processors can scan racks 01-03.

PLCĆ5/25 and PLCĆ5/30 processors can scan racks 01-07.

PLCĆ5/40 and PLCĆ5/40L processors can scan racks 01-17.

PLCĆ5/60 and PLCĆ5/60L processors can scan racks 01-27.

PLCĆ5/250 processors can scan racks 00-37.

PLCĆ3 processors can scan racks 00-76.

Note 1 - W hen using a 1794ĆASB series C (or later) adapter module, rack addresses 40 to 76 are only available in Standard and

Standard-32 modes.