Rockwell Automation 1794-ASB/E Remote I/O Adapter Module User Manual User Manual

Page 58

Advertising
background image

Specifications

A–2

Publication 1794ĆĆUM009D-EN-P - April 2004

1794ĆASB Series E Specifications

Surge Transient Immunity

IEC 61000-4-5

+1kV line-line (DM) and +2kV line-earth (CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6

10V rms with 1kHz sine wave 80% AM from 150kHz to 80MHz

Emissions

CISPR 11

Group 1, Class A (with appropriate enclosure)

Enclosure Type Rating

None (open-style)

Remote I/O Cable

Belden 9463 or equivalent as specified in publication ICCGĆ2.2

Remote I/O Connector Plug

Part Number 942029-03

Power Conductors

Wire Size

Category

12 gauge (4mm

2

) maximum sokid or stranded wire rated at 75

o

C or greater

3/64 inch (1.2mm) insulation max.

2

1

Agency Certification

(when product is marked)

ULUL

L

isted Industrial Control Equipment

UL

UL Listed for Class I, Division 2 Group A, B, C and D Hazardous Locations

CSA

CSA Certified Process Control Equipment for Class I, Division 2 Group A, B,

C, D Hazardous Locations

EEx

2

European Union 94/9/EEC ATEX Directive, compliant with

EN 50021; Potentially Explosive Atmospheres, Protection n"

CE

2

European Union 89/336/EEC EMC Directive, compliant with:

EN 50081-2, Industrial Emissions

EN 50082-2, Industrial Immunity

EN 61326, Meas./Control/Lab., Industrial Requirements

EN 61000-6-2, Industrial Immunity

C-Tick

2

Australian Radiocommunications Act,compliant with:

AS/NZS 2064, Industrial Emissions

Publications

Installation Instructions 1794-IN046

1 Use this conductor category information for planning conductor routing. Refer to publication

1770Ć4.1, Industrial Automation Wiring and Grounding Guidelines."

2

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and

other certification details