Primary rack, Complementary rack – Rockwell Automation 1794-ASB/E Remote I/O Adapter Module User Manual User Manual
Page 33

2–15
Installing Your Remote I/O Adapter Module
Publication 1794ĆUM009D-EN-P - April 2004
Use the following table to set your address switches for
complementary I/O when using a PLC-5 processor. For all other
processors, refer to the programming manual for that specific
processor.
Primary Rack
Rack Number
S1 Switch Position
1747ĆSN
PLCĆ5
6
5
4
3
2
1
Rack 0
Not Valid
ON
ON
ON
ON
ON
OFF
Rack 1
Rack 1
OFF
ON
ON
ON
ON
OFF
Rack 2
Rack 2
ON
OFF
ON
ON
ON
OFF
Rack 3
Rack 3
OFF
OFF
ON
ON
ON
OFF
Rack 4
ON
ON
OFF
ON
ON
OFF
Rack 5
OFF
ON
OFF
ON
ON
OFF
Rack 6
ON
OFF
OFF
ON
ON
OFF
Rack 7
OFF
OFF
OFF
ON
ON
OFF
Complementary Rack
Rack Number
S1 Switch Position
1747ĆSN
PLCĆ5
6
5
4
3
2
1
Rack 0
Not Valid
ON
ON
ON
OFF
ON
ON
Rack 1
Rack 1
OFF
ON
ON
OFF
ON
ON
Rack 2
Rack 2
ON
OFF
ON
OFF
ON
ON
Rack 3
Rack 3
OFF
OFF
ON
OFF
ON
ON
Rack 4
ON
ON
OFF
OFF
ON
ON
Rack 5
OFF
ON
OFF
OFF
ON
ON
Rack 6
ON
OFF
OFF
OFF
ON
ON
Rack 7
OFF
OFF
OFF
OFF
ON
ON
In this chapter you learned how to install your adapter module and
set your switches. Chapter 3 tells you how to communicate with your
system.
Setting the Address
Switches for
Complementary I/O
Chapter Summary