Primary rack, Complementary rack – Rockwell Automation 1794-ASB/E Remote I/O Adapter Module User Manual User Manual

Page 33

Advertising
background image

2–15

Installing Your Remote I/O Adapter Module

Publication 1794ĆUM009D-EN-P - April 2004

Use the following table to set your address switches for
complementary I/O when using a PLC-5 processor. For all other
processors, refer to the programming manual for that specific
processor.

Primary Rack

Rack Number

S1 Switch Position

1747ĆSN

PLCĆ5

6

5

4

3

2

1

Rack 0

Not Valid

ON

ON

ON

ON

ON

OFF

Rack 1

Rack 1

OFF

ON

ON

ON

ON

OFF

Rack 2

Rack 2

ON

OFF

ON

ON

ON

OFF

Rack 3

Rack 3

OFF

OFF

ON

ON

ON

OFF

Rack 4

ON

ON

OFF

ON

ON

OFF

Rack 5

OFF

ON

OFF

ON

ON

OFF

Rack 6

ON

OFF

OFF

ON

ON

OFF

Rack 7

OFF

OFF

OFF

ON

ON

OFF

Complementary Rack

Rack Number

S1 Switch Position

1747ĆSN

PLCĆ5

6

5

4

3

2

1

Rack 0

Not Valid

ON

ON

ON

OFF

ON

ON

Rack 1

Rack 1

OFF

ON

ON

OFF

ON

ON

Rack 2

Rack 2

ON

OFF

ON

OFF

ON

ON

Rack 3

Rack 3

OFF

OFF

ON

OFF

ON

ON

Rack 4

ON

ON

OFF

OFF

ON

ON

Rack 5

OFF

ON

OFF

OFF

ON

ON

Rack 6

ON

OFF

OFF

OFF

ON

ON

Rack 7

OFF

OFF

OFF

OFF

ON

ON

In this chapter you learned how to install your adapter module and
set your switches. Chapter 3 tells you how to communicate with your
system.

Setting the Address

Switches for

Complementary I/O

Chapter Summary