Installing Your Remote I/O Adapter Module

Publication 1794ĆUM009D-EN-P - April 2004

Connect external wiring to the remote I/O adapter as shown below.

1 SH 2

B

C

D

A

20131

24V

COM

AllenĆBradley

24 VDC

POWER SUPPLY

RIO ADAPTER

1794-ASB

ADAPTER

ACTIVE FAULT

LOCAL

FAULT

Termination resistor (if required)

82

or 150

(refer to your processor

documentation for size and usage)

PWR

1. Connect the remote I/O cable to the removable plug-in remote

I/O connector.

Connect

To

Blue Wire - RIO

1

Shield Wire - RIO

SH

Clear Wire - RIO

2

ATTENTION

!

If this is the last adapter in your FLEX I/O
system, or the last adapter on the remote I/O link,
you must use a termination resistor across
terminals 1 and 2 on the remote I/O connector.
Refer to the information supplied with the
processor being used for information on the size
of the resistor.

2. Connect +24V dc input to the left side of the lower connector

terminal A.

3. Connect 24V common to the left side of the upper connector

terminal B.

4. Connections C and D are used to pass 24V dc power and

common to the next module in the series (if required).

Wiring when total current draw is less than 10A

DaisyĆchaining

24Vdc

Note: Refer to the individual instructions for each module for actual wiring information.

Note: Modules must be either all analog or all discrete. Do not mix analog

and discrete modules when using the daisyĆchain wiring scheme.

For Example: