Kinetix 6200 and Kinetix 6500 IAM and AM Power Modules 5

Rockwell Automation Publication 2094-IN011D-EN-P - August 2013

Set the Ground Jumper

Follow these steps to set the ground jumper for ungrounded power.

1. Remove the top and bottom front-panel cover screws.

Refer to the figure on

page 6

for an illustration of your actual hardware.

2. Pull the front panel cover straight out, as shown, and locate the ground jumper.

3. Move the ground jumper.

4. Replace the IAM power module front panel cover and two screws.

Apply 1.6 N•m (14 lb•in) torque.

5. Mount the IAM power module back on the power rail.

Refer to

Mount the IAM/AM Power Modules

on

page 9

for help mounting your IAM

module.

TIP

Access to the jumper improves when the Bulletin 2094 control module is removed
from the IAM power module.

To remove the control module from the IAM power module, refer to the Kinetix 6200
and Kinetix 6500 Modular Servo Drives User Manual, publication

2094-UM002

.

IAM Power Module

Configuration

Grounded (default)

Ungrounded

2094-BC01-MP5-M (460V)

P16 and P17

P18 and P19

2094-BC01-M01-M (460V)

2094-BC02-M02-M (460V)

2094-BC04-M03-M (460V)

2094-BC07-M05-M (460V)