Rockwell Automation 9329 Drive Application Software Tension Control Gen. Units User Manual

Page 24

Advertising
background image

FM – Tension Control

Drive Application Software – page 24 of 52

4.5.16 TrimLimSpdZero_Pct

This is the amount of speed trim the regulator will output at zero speed. This value is
in percent of Maximum Line Speed.
Usage – This value is typically 1 to 2 %. Connect to the Trim Limit at Zero speed
value tag. Or set the constant value in the JSR.

4.5.17 LineSpdTrimLimSpd_Pct

This is the line speed where the trim limit output will be equal to TrimLimSpd_Pct. As
the line speed is increased from zero to this value, the trim limit output is
incrementing from TrimLimSPdZero_Pct to TrimLimSpd_Pct. This value is entered
as a percent of maximum line speed.
Usage – Connect to the Line Speed Maximum for trim reference tag or set the
constant value in the JSR.

4.5.18 TrimLimTrq_Pct

This is the trim limit when the trim regulator is acting in torque control. It is entered
as percent of maximum tension for the section.
Usage – This value is typically 20 to 30%. Connect to the Trim Limit Torque tag or set
the constant value in the JSR.

4.5.19 TrimRate_PctSec

When the trim regulator is turned off, the output is ramped from the current value to
zero. The decrement rate is determined by TrimRate_PctSec. This is part of “bump
less” transfer for the tension control circuit.
Usage - Set this value to avoid sudden changes in tension when the regulator is
switched off. This is used when the system is changed to sensor less mode.

Line Speed

Trim Limit Percent

TrimLimSpd_Pct

LineSpdTrimLimSpd_Pct

0

Advertising