4 trimfbwlead_rad, 5 trimfbwlag_rad – Rockwell Automation 9329 Drive Application Software Tension Control Gen. Units User Manual

Page 44

Advertising
background image

FM – Tension Control

Drive Application Software – page 44 of 52

6.3.4 TrimFbWLead_Rad

This the Lead frequency in rad/second of the feedback filter. It is typically set to the
speed loop bandwidth (p97 in the PowerFlex 700S) to cancel the lag effect of the
velocity loop.

6.3.5 TrimFbWLag_Rad

This is the Lag frequency in rad/second of the feedback filter. It is typically set to five
times the lead frequency set above.