FM – Tension Control
Drive Application Software – page 44 of 52
6.3.4 TrimFbWLead_Rad
This the Lead frequency in rad/second of the feedback filter. It is typically set to the
speed loop bandwidth (p97 in the PowerFlex 700S) to cancel the lag effect of the
velocity loop.
6.3.5 TrimFbWLag_Rad
This is the Lag frequency in rad/second of the feedback filter. It is typically set to five
times the lead frequency set above.