2-Axis Servo Module M/N 57C422B

Step 13.

Verify power supply connections by performing
the following operations:

a. Make certain that all connectors from the

module and the encoders are disconnected.

b. Turn on power to the system.

c. Verify that you can read 5 volts on the proper

terminal strip and encoder connectors
(terminals 1 and 2).

d. Verify that you can read ±12 volts or ±15 volts

on the proper terminal strip connectors
(terminals 21, 22, 23).

e. Turn off power and reattach the connectors to

the module.

Step 14.

Verify power supply connections at the encoder by
performing the following operations:

a. Make certain that all connectors at the

encoders are disconnected.

b. Turn on power to the system.

Figure 3.8 – Typical Drive Fault Connections

DANGER

ADJUSTMENTS ARE MADE WITH THE POWER ON.
EXERCISE EXTREME CAUTION AS HAZARDOUS VOLTAGE
EXISTS. FAILURE TO OBSERVE THIS PRECAUTION COULD
RESULT IN SEVERE BODILY INJURY OR LOSS OF LIFE.