PROFIBUS DP Communications

11

Publication 2711-6.3

Type B Cable Termination

If the PanelView is the last device on an end of a network, it must be
terminated at the PROFIBUS DP connector or T-junction. Use the
recommended terminating blocks (page 9).

If you do not have terminating blocks available, terminate the cable
as shown below.

+5V Pin# 6

+ Receive/ Transmit

Pin #3

Data Ground Pin #5

– Receive/ Transmit

Pin #8

390 ohms (2%,



1

/

4

watt)

150 ohms
(2%,



1

/

4

watt)

390 ohms (2%,



1

/

4

watt)

Cable

Note: The bus cable should be grounded to an earth ground only at
one point on the network.