PROFIBUS DP Communications

34

Publication 2711-6.3

Alert Number

Corrective Action(s)

Type

Meaning

7

The DP Master is in ‘clear’ mode.

Comms

Warning

1. Place DP Master in operate mode.

8

The PanelView was just locked by a DP Master.

Comms

Warning

No action required.

9

DP Master requested an unexpected block.

“Reminder”

Message.

1. Make sure the DP Master’s code only requests

blocks defined by the PanelView application.

2. Check that the correct PanelView application is

loaded for the DP Master.

3. Check the extended diagnostics to obtain the block

number that caused the problem.

10

DP Master sent an unexpected block.

“Reminder”

Message.

1. Make sure the DP Master’s code only sends blocks

defined by the PanelView application.

2. Check that the correct PanelView application is

loaded for the DP Master.

3. Check the extended diagnostics to obtain the block

number that caused the problem.

11

No DP Master on the wire or cable is disconnected.

Comms

Warning

1. Check cable connections.
2. Make sure DP Master is operating.

12

Check configuration error. The slave is unlocked (refer
to glossary).

Comms

Warning

1. Make sure the DP Master is configured correctly for

the loaded PanelView application. The expected
configuration may be found in the extended
diagnostics.

2. Check that the correct PanelView application is

loaded for the DP Master.

13

Set parameter error. The slave is unlocked.

Comms

Warning

1. Verify the WD value is valid.
2. Verify that the system reaction time is valid.
3. Verify the identification number is valid.
4. Verify that the user parameter data length is correct.

14

A type error was detected in the configuration bytes
sent by the DP Master. The slave is unlocked.

Comms

Warning

1. Check extended diagnostics for more information.

15

A consistency error was detected in the configuration
bytes sent by the DP Master. The slave is unlocked.

Comms

Warning

1. Check extended diagnostics for more information.

16

A format error was detected in the configuration bytes
sent by the DP Master. The slave is unlocked.

Comms

Warning

1. Check extended diagnostics for more information.

17

A length error was detected in the configuration bytes
sent by the DP Master. The slave is unlocked.

Comms

Warning

1. Check extended diagnostics for more information.

18

SPC fault.

Critical Fault.

1. Reset the PanelView. If this condition persists, the

PROFIBUS communication card needs to be
replaced. Contact Allen-Bradley for service.

19

One or more startup tests failed.

Critical Fault.

1. Reset the PanelView. If this condition persists, the

PROFIBUS communication card needs to be
replaced. Contact Allen-Bradley for service.

20

Internal error.

Critical Fault

Contact Allen-Bradley for assistance.