PROFIBUS DP Communications

17

Publication 2711-6.3

Multiplex Module Handshaking

It is the DP Master’s role to manage the handshake operation. This
is accomplished by initiating an exchange using the multiplex output
module’s control word and monitoring progress of the exchange in
the multiplex input module’s status word. The timing diagram
below shows the operation of the Handshake Bit controlled by the
DP Master and the one controlled by the PanelView terminal.

PanelView
Input Handshake Bit

DP Master
Output Handshake Bit

DP Master sends/requests new data

PanelView acknowledges reception of data / sends requested data

DP Master resets handshake bit

PanelView ready to process new data / request

Time

Command Word / Handshake Bit

Status Word / Handshake Bit