Profibus dp network specifications – Rockwell Automation 2711 PanelView 550/900 Profibus Communications User Guide User Manual
Page 39

PROFIBUS DP Communications
39
Publication 2711-6.3
The following specifications apply to the PanelView terminal on a
PROFIBUS DP network:
General Specifications
Item
Specification
Communication Standard
PROFIBUS – DIN 19245 Part 1, Issue 1991 and
Draft DIN 19245 Part 3, Issue 1993
PROFIBUS DP Supported Baud
Rates
9.6, 19.2, 93.75, 187.5, 500k bits/s and 1.5M bits/s
PROFIBUS DP Identification
Number
6714 (Hex)
Station Delay Response Times (Tsdr)
Baud Rate
Minimum
T
sdr
Maximum
T
sdr
9.6k bit/s, 19.2k bit/s, 93.7k bit/s, 187.5k bit/s
11 bit times
60 bit times
500k bit/s
11 bit times
100 bit times
1.5M bit/s
11 bit times
150 bit times
Supported DP Data Sizes
Data Type
Maximum
Data Size (bytes)
Input Data
64
Output Data
64
Extended Diagnostic Data
14
User Operational Parameters
Not Used
Maximum Number of Modules
4
Maximum Required Consistency
32
Supported DP Features
Feature
Supported/Not Supported
Freeze Mode
Not Supported
Sync. Mode
Not Supported
Auto Baud
Supported
Set Slave Address
Not Supported
PROFIBUS DP Network
Specifications