Profibus dp network specifications – Rockwell Automation 2711 PanelView 550/900 Profibus Communications User Guide User Manual

Page 39

Advertising
background image

PROFIBUS DP Communications

39

Publication 2711-6.3

The following specifications apply to the PanelView terminal on a
PROFIBUS DP network:

General Specifications

Item

Specification

Communication Standard

PROFIBUS – DIN 19245 Part 1, Issue 1991 and
Draft DIN 19245 Part 3, Issue 1993

PROFIBUS DP Supported Baud
Rates

9.6, 19.2, 93.75, 187.5, 500k bits/s and 1.5M bits/s

PROFIBUS DP Identification
Number

6714 (Hex)

Station Delay Response Times (Tsdr)

Baud Rate

Minimum

T

sdr

Maximum

T

sdr

9.6k bit/s, 19.2k bit/s, 93.7k bit/s, 187.5k bit/s

11 bit times

60 bit times

500k bit/s

11 bit times

100 bit times

1.5M bit/s

11 bit times

150 bit times

Supported DP Data Sizes

Data Type

Maximum

Data Size (bytes)

Input Data

64

Output Data

64

Extended Diagnostic Data

14

User Operational Parameters

Not Used

Maximum Number of Modules

4

Maximum Required Consistency

32

Supported DP Features

Feature

Supported/Not Supported

Freeze Mode

Not Supported

Sync. Mode

Not Supported

Auto Baud

Supported

Set Slave Address

Not Supported

PROFIBUS DP Network
Specifications