PROFIBUS DP Communications

20

Publication 2711-6.3

Note: Performing a multiplex module data exchange requires a
number of poll cycles from the DP Master to the PanelView
terminal. During each of those poll cycles real time data is
constantly being exchanged.

The diagram below shows the relative position of the Real Time and
Multiplex modules in the data packet sent between the DP Master
and the PanelView terminal. The modules reside in the DP Master’s
database in the same relative position.

Real Time Output Data

Hsk

BlockOut

BlockIn

Multiplex Block Output Data

DP Master to PanelView

Real Time Input Data

Hsk

BlockOut

BlockIn

Multiplex Block Input Data

PanelView to DP Master

Up to 16 Words

1 Word

15 Words

Up to 16 Words

1 Word

15 Words

Real Time Module:

Multiplex Module:

Hsk:

Handshake Bit

BlockOut:

Block ID sent by DP Master (7 bits)

BlockIn:

Block ID requested by DP Master (7 bits)

Block Data

Real Time Module:

Multiplex Module:

Hsk:

Handshake Bit

BlockOut::

Block ID received by PanelView (7 bits)

BlockIn:

Block ID sent by PanelView (7 bits)

Block Data