Sizing the enclosure – Rockwell Automation 7703E Medium Voltage SMC OEM Components - 10-15 kV User Manual

Page 12

Advertising
background image

12

Rockwell Automation Publication 7703E-IN001E-EN-P - July 2014

Chapter 3

PowerBrick™ Installation

In addition to the PowerBricks, a voltage sensing board is to be connected in the
power circuit.

Table 2

lists the voltage sensing board catalog numbers.

Table 2 - Voltage Sensing Board Catalog Number

Sizing the Enclosure

Use the data in

Table 3

to assist in calculating the enclosure size.

Table 3 - PowerBrick Specifications

Catalog Number

Voltage Sensing Board Input (3 phase, 50/60 Hz)

7703E-VSM

10,000…12,000V

7703E-VSN

12,001…14,400V

ATTENTION: The enclosure for the power stack assemblies must be adequately
sized to provide sufficient airflow to cool the units. Failure to provide adequate
cooling may result in reduced duty cycles or component failure.

Description

160 A, 340 A

Input Voltages
(50/60 Hz)

10,000…12,000V
12,001…14,400V
3 phase, +10%, -15%

Ambient Temperature

0 °C…40 °C (32 °F…104 °F)

Power Section
(for 3 phases)

30 SCR at 10…12 kV
36 SCR at 12.1…14.4 kV

Repetitive Peak Inverse
Voltage Rating

10 to12 kV…32,500 PIV
12.1…14.4 kV…39,000 PIV

Thermal Capacity

(1)

600% of FLA, 10 seconds
450% of FLA, 30 seconds

dv/dt Protection

R.C. Snubber Network

Maximum Heat
Dissipation (kW)

Start or Stop Cycle (at 450% FLA)

160 A

340 A

580 A

Continuous

(2)

10,000…12,000V

27

57

98

0.5

12,001…14,400V

32

69

117

0.5

Altitude

0…1000 m (0…3,300 ft)
(See Controller Deratings Table on page 6, Publication

1503-BR010F-EN-P

)

Net Shipping Weight
(3 phases)

Rating (kV)

10…12

12.1…14.4

Weight
kg (lbs)

570 (1260)

684 (1512)

(1) It may be possible to offer extended start times at reduced current or ambient temperature. Please consult Rockwell Automation factory for assistance.

(2) After bypass contactor/breaker is closed.