Voltage sensing board dimensions, Mounting and connecting the voltage sensing board – Rockwell Automation 7703E Medium Voltage SMC OEM Components - 10-15 kV User Manual

Page 21

Advertising
background image

Rockwell Automation Publication 7703E-IN001E-EN-P - July 2014

21

PowerBrick™ Installation

Chapter 3

Voltage Sensing Board
Dimensions

Figure 7 - Voltage Sensing Board Dimension Diagram

Mounting and Connecting
the Voltage Sensing Board

The voltage sensing board (VSB) for the relevant voltage range (see table below)
should be mounted adjacent to the PowerBrick (refer to

Figure 7

for

dimensions). All connection points are to be made accessible.

Connect the voltage sensing board to the L1 to L3 (Line) and T1 to T3 (Load)
terminals of the power stack (refer to

Figure 8

and

Chapter 6

).

Recommended specifications for wire used on medium voltage connections: UL
style 3239, #18 AWG, 40 KVDC silicone rubber insulated wire, covered with
PCV tubing or other suitable material.

8.9 [0.35]
4 holes

Includes features to secure
HV wire for maintained spacings.

Approximate dimensions in mm [inches]

Description

Line Voltage
(3 phase, 50/60 Hz)

MV Ratio

Catalog Number

Voltage Sensing Board

10,000…12,000V

126

7703E-VSM

12,001…14,400V

97

7703E-VSN

IMPORTANT

The wires must be prevented from touching live or grounded metals, and low
voltage wiring, or have supplemental insulation suitable for the application.
Use the tapered features below the Lx and Tx terminals to maintain wire
spacings in this area.

Advertising