Rockwell Automation 7703E Medium Voltage SMC OEM Components - 10-15 kV User Manual

Page 32

Advertising
background image

32

Rockwell Automation Publication 7703E-IN001E-EN-P - July 2014

Chapter 4

Control Component Installation

Table 7 - Terminal Descriptions

Note: The OFF state leakage current for a solid-state device connected to an
SMC Flex input must be less than 6 mA.

Connecting Interface Board
to Voltage Sensing Board

Use the wire harness provided to connect the Voltage Sensing Board and the
Interface Board. Refer to

Figure 14

for the location of the connector on the

interface board, and

Figure 8 on page 22

for the connector on the voltage sensing

board.

Terminal Number

Description

Terminal Number

Description

11

Control Power Input C

23

PTC Input

12

Control Power Common C

24

PTC Input

13

Control Enable Input

(1)

25

Tach Input ( - )

14

Control Module Ground

26

Tach Input ( + )

15

Option Input #2

27

Ground Fault Transformer Input

16

Option Input #1

28

Ground Fault Transformer Input

17

Start Input

29

Aux. Contact #2

18

Stop Input

30

Aux. Contact #2

19

Aux. Contact #1 (Ext. Bypass)

(2)

31

Aux. Contact #3

20

Aux. Contact #1 (Ext. Bypass)

32

Aux. Contact #3

21

Not Used

33

Aux. Contact #4 (Normal)

(3)

(4)

22

Not Used

34

Aux. Contact #4 (Normal)

(1) Do not connect any additional loads to these terminals. These “parasitic” loads may cause problems with operation, which may result in false starting and stopping.

(2) Aux. Contact #1 is always programmed for Ext. Bypass (N.O.) to control the bypass contactor in MV applications.

(3) Aux. Contact #4 is always programmed for “Normal” (N.O.) to control the isolation contactor in MV applications.

(4) RC snubbers are required on inductive loads connected to auxiliary.