4 - control component installation, Interface board installation, Chapter 4 – Rockwell Automation 7703E Medium Voltage SMC OEM Components - 10-15 kV User Manual
Page 27: Control component installation, Chapter

Rockwell Automation Publication 7703E-IN001E-EN-P - July 2014
27
Chapter
4
Control Component Installation
Interface Board Installation
Mount the 7703E-INTB Interface Board in a suitable location within a low
voltage compartment, using the appropriate hardware. Use the interface board
mounting bracket (refer to
).
Figure 13 - Mounting the Interface Board
ATTENTION: Do not mount the interface board in the same compartment as
high voltage components. Ensure that barriers are provided in the final
application to prevent access to any live high-voltage parts, including insulated
conductors located in enclosures with low voltage parts and wiring. Failure to
do so may result in severe burns, injury or death.
Top mounting holes
for SMC Flex
Control Module
Front View
Side View
Mounting holes (4)
7.14 mm [0.281 in.] dia.
Bottom mounting holes for
SMC Flex Control Module
Approximate dimensions in mm [inches]