Control Component Installation

Interface Board Installation

Mount the 7703E-INTB Interface Board in a suitable location within a low
voltage compartment, using the appropriate hardware. Use the interface board
mounting bracket (refer to

Figure 13

).

Figure 13 - Mounting the Interface Board

ATTENTION: Do not mount the interface board in the same compartment as
high voltage components. Ensure that barriers are provided in the final
application to prevent access to any live high-voltage parts, including insulated
conductors located in enclosures with low voltage parts and wiring. Failure to
do so may result in severe burns, injury or death.

Top mounting holes
for SMC Flex
Control Module

Front View

Side View

Mounting holes (4)
7.14 mm [0.281 in.] dia.

Bottom mounting holes for
SMC Flex Control Module

Approximate dimensions in mm [inches]