A - component deratings, Deratings specifications, Appendix a – Rockwell Automation 7703E Medium Voltage SMC OEM Components - 10-15 kV User Manual
Page 47: Component deratings, Appendix
Rockwell Automation Publication 7703E-IN001E-EN-P - July 2014
47
Appendix
A
Component Deratings
Deratings Specifications
The components described in this publication may be applied in a wide variety of
situations. Some applications may require component derating. For example, at
altitudes above 1000 m (3300 ft), the maximum current and basic impulse level
(BIL) are reduced as shown in
.
Table 10 - Component Derating Table
Altitude Rating
Reduce Max. Continuous Current Rating by:
B.I.L. Withstand Rating
160 A c
340 A
580 A
12 kV
15 kV
0…1000 m
(0…3300 ft)
—
—
75 kv
95 kV
1001…2000 m
(3301…6600 ft)
5 A
10 A
15 A
66 kV
84 kV
2001…3000 m
(6601…9900 ft)
10 A
20 A
30 A
59 kV
74 kV
3001…4000 m
(9901…13,200 ft)
15 A
30 A
45 A
52 kV
66 kV
4001…5000 m
(13,201…16,500 ft)
20 A
40 A
60 A
46 kV
58 kV