Plantpax appserv-ows base configuration – Rockwell Automation 9528-APPOWSENE Virtual Image Templates User Manual User Manual

Page 83

Advertising
background image

Rockwell Automation Publication 9528-UM001C-EN-P - March 2014

83

Configure Application Server OWS (Microsoft Remote Desktop Services)

Chapter 4

When the FactoryTalk View SE Server is also the Remote Desktop Session
Host, it is possible that thin clients cannot add/change pens in a trend.

If your FactoryTalk View SE client configuration (.cli) enables 'Show
Diagnostics List', the list shows all activity from all clients running on the
same Remote Desktop Session Host. This is due to the fact that although
each instance of the FactoryTalk View SE client runs in a separate session,
they are all hosted on the same computer and share common log resources.
This can be confusing for HMI operators because they see diagnostic
activity on their client that they did not initiate.

Using the Tag Import and Export Wizard does not work correctly when
used in a Remote Desktop Client session. Run this wizard only from a
FactoryTalk View Studio instance on the HMI Server console. Using a
Remote Desktop Client to connect to the console session can avoid this
issue, but is not recommended.

PlantPAx AppServ-OWS Base Configuration

TIP

For more information see Knowledgebase Answer ID 32715 - Cannot
add/change pens in trend from SE client on Terminal Server at

https://rockwellautomation.custhelp.com/app/answers/detail/a_id/
32715

.

IMPORTANT

You can add additional role services to your server depending on your specific
deployment of Remote Desktop Services and connectivity needs. This can add
additional configuration beyond which this base Remote Desktop Server has
been configured for.

Advertising