Analog alarm – Rockwell Automation MMCL Using the Mining, Mineral, and Cement Library (MMCL) in FactoryTalk View Site Ed User Manual

Page 48

Advertising
background image

Publication RA-UM001B-EN-P - November 2010

48 Developing an HMI Application

Analog Alarm

The standard configuration uses four thresholds, defined as follows.

An alarm is not clearable until the device in alarm is back in a normal state.
The analog alarm value H123\H456\H78\Val\PVA stays at the alarm level,
until it has been acknowledged by the operator with the display acknowledge
button

.

An analog alarm counts as 1 alarm, even if two messages are visible in

the alarm list (for example, High-alarm and Max-alarm).

Threshold

Severity

Alarm Label

Direction

H123\H456\H78\Set\NV

1

H123-H456.H78:NA

Decreasing

H123\H456\H78\Set\LV

2

H123-H456.H78:LA

Decreasing

H123\H456\H78\Set\HV

2

H123-H456.H78:HA

Increasing

H123\H456\H78\Set\MV

1

H123-H456.H78:MA

Increasing