Maximum data overlap – Rockwell Automation FactoryTalk Historian SE 3.0 UniInt Interface User Guide User Manual

Page 103

Advertising
background image

UniInt Interface User Manual

97

Refer to Figure 7,below which describes the failover action when both interface copies start
at the same time and the latency for an update to the data source is equal to one half of an
update interval.

A

Point Values

1

2

3

4

Time

1 Second

Intervals

C

B

D

15
14
13
12
11

...

4
3
2
1
0

0
1
2

IF1

State

Primary

Backup
Off

Primary

Backup

Off

0

15
14
13
12
11

...

4
3
2
1
0

IF1

Heartbeat

IF2

State

IF2

Heartbeat

Active_ID

Time

Action

T+0

Neither interface is running

T+1

Event A: IF1 starts and notices the
active ID point is 0 so it transitions
to active and writes a 1 to the
active ID point.

T+1.25

Event B: IF2 starts and notices the
active ID point is 0 so it transitions
to active and writes a 2 to the
active ID.

T+1.5

Event C: the update from IF1
reaches the data source

T+2

Event D: IF1 reads a 1 for the
active ID point. Immediately after
this, the update from IF2 reaches
the data source.

T+2.5

IF2 reads a 2 for the active ID point
and remains in the active mode.

T+3

IF1 reads a 2 for the active ID and
immediately transitions to the
backup role.

The last interface to update the active ID
point is the interface that will remain in the
primary role.

Figure 7: Timing chart for both interfaces starting at the same time.

Maximum Data Overlap

Figure 8 shows the timing chart for a scenario that allows the maximum overlapping of data
during a failover.

Error! Objects cannot be created from
editing field codes.