UniInt Interface User Manual

93

B

A

C

Point Values

B

1

2

3

4

Time

1 Second

Intervals

31
30
29

18
17

-

14
13

...

1
0

0
1
2

IF1

State

Primary

Backup
Off

Primary

Backup

Off

0

15
14
13
12
11

...

4
3
2
1
0

IF1

Heartbeat

IF2

State

IF2

Heartbeat

Time

Action

T+0

Both interfaces are running with IF1 in
the primary role.

T+2.5

IF2 reads the active ID point and IF1‟s
heartbeat point. Both are good, so IF2
discards data older than time 0.5.

T+3

Event A: IF1 updates its heartbeat to 30
because it has lost its connection to the
Historian Server. When the connection
to Historian is lost, the heartbeat for the
interface increments between 17-31
and then back to 17. In this example
the primary interface copy heartbeat
was at 13 for IF1, so the next heart beat
will be 30 if the connection to Historian
is lost.

T+3.5

Event B: IF2 reads the active ID point
and IF1‟s heartbeat point. IF2 still has a
good connection to Historian, so it
transitions to primary and sets the
active ID point to 2.

T+4

Event C: IF1 reads the active ID point
and notices the change to a 2. IF1
immediately transitions to backup.

Overlap data from time 0.5 to 4

Figure 5: Timing chart for failover when the primary interface loses its connection with the
Historian Server.