Rockwell Automation FactoryTalk Historian SE 3.0 UniInt Interface User Guide User Manual

Page 93

Advertising
background image

UniInt Interface User Manual

87

15
14
13
12
11

...

4
3
2
1
0

Active_ID

0
1
2

IF1

State

Primary

Backup
Off

Primary

Backup

Off

1

2

3

4

Time

B

A

0

Point Values

1 Second

Intervals

B

15
14
13
12
11

...

4
3
2
1
0

IF1

Heartbeat

IF2

State

IF2

Heartbeat

Time

Action

T+0

Both interfaces are running with IF1 in
the primary role.

T+2.5

IF2 reads the active ID point and IF1‟s
heartbeat point. Both are good so IF2
discards data in its queue older than
time 0.5.

T+2.8

Event A: IF1 shuts down gracefully,
setting the active ID point and its
heartbeat point to 0.

T+3.5

Event B: IF2 notices the active ID point
is 0 and immediately transitions to
primary, sending the data in its queue to
Historian.

Overlap data from time 0.5 to 2.8

Figure 2: Timing chart for when the primary interface gracefully shuts down and the backup
interface assumes the role of primary.