UniInt Interface User Manual

13

Parameter

Description

/stopstat=digstate

or

/stopstat

/stopstat

only is

equivalent to

/stopstat="Intf
Shut"

Optional

Default = no digital state
written at shutdown.

If the

/stopstat

parameter is present on the startup

command-line, then the digital state

Intf Shut

will be

written to each Historian Point when the interface is stopped.

If

/stopstat=digstate

is present on the command-line,

then the digital state,

digstate

, will be written to each

Historian Point when the interface is stopped. UniInt uses the
first occurrence in the table.

If neither

/stopstat

nor

/stopstat=digstate

is

specified on the command-line, then no digital states will be
written when the interface is shut down.

Examples:

/stopstat=shutdown
/stopstat="Intf Shut"

The entire

digstate

is enclosed within double quotes when

there is a space in

digstate

.

/uht_id=#

Optional

Default = Health tags are not
filtered by location3 unless
UniInt failover is used

The

/uht_id=#

command-line parameter is used to specify

a unique ID for interfaces that are run in a redundant mode
without using the UniInt failover mechanism. There are
several Rockwell Automation interfaces that are UniInt based
and implement their own version of failover. In order for health
tag(s) to be configured to monitor a single copy of the
interface, an additional parameter is required. If the

/uht_id=#

is specified, only health tags with a location3

value =

#

will be loaded.

/uiinfops=s

Optional (not recommended)

Default = UI_IF_INFO

The

/uiinfops

command-line parameter is used in

conjuction with the Interface Informaiton point and is
described in more detail in the Interface Monitoring Points
section. The interface by default looks for a point with the
point source UI_IF_INFO and checks to see if the point is the
Interface Monitoring point. This point source can be changed
but if it is, the

/uiinfops

will have to be added to every

interface in order for the interfaces to find the Interface
Information point.

/uitrace=x

Optional

Default = no tracing enabled

If the

/uitrace

command-line parameter is specified, the

values and timestamps that are received by the interface are
also written to the log file. Tracing can be enabled for a
particular point by specifying /uitrace=x, where x is the point
number or tag name of the point to be traced. This parameter
should be used with caution because specifying this
parameter could cause the log file to become very large.