UniInt Interface User Manual

91

1

2

3

4

Time

B

A

Point Values

1 Second

Intervals

C

15
14
13
12
11

...

4
3
2
1
0

0
1
2

IF1

State

Primary

Backup
Off

Primary

Backup

Off

0

15
14
13
12
11

...

4
3
2
1
0

IF1

Heartbeat

IF2

State

IF2

Heartbeat

Active_ID

Time

Action

T+0

Both interfaces are running with
IF1 in the primary role.

T+2.5

IF2 reads the active ID point and
IF1‟s heartbeat point. Both are
good, so IF2 discards data in its
queue older than time 0.5.

T+2.8

Event A: the active ID point on the
data source is changed from 1 to
2.

T+3

Event B: IF1 reads the active ID
point and IF2‟s heartbeat point.
IF2‟s heartbeat is good and the
active ID has changed to a 2, so
IF1 immediately transitions to
backup.

T+3.5

Event C: IF2 notices that the
active ID point on the data source
is 2 and immediately transitions to
primary. The data in its queue and
any new data are sent to
Historian.

Overlap data from time 0.5 to 3.

Figure 4: Timing chart for a manual failover to the backup interface.