Standard parameters – Rockwell Automation FactoryTalk Historian SE 3.0 UniInt Interface User Guide User Manual

Page 11

Advertising
background image

UniInt Interface User Manual

5

Standard Parameters

These command-line parameters are used in the every-day running of an interface. This table
does not contain the entire list of parameters supported by UniInt. There are parameters that
are specific to configuring disconnected start-up discussed in the Disconnect Start up section
(page 54) and parameters specific to configuring UniInt Failover discussed in Configuring
UniInt Failover
section (page75). None of the parameters are case sensitive. For example,
/ps=ifc is equivalent to /ps=IFC.

Parameter

Description

/AppName=Name

Optional

Default = 1st four
characters of the
interface executable

The

/AppName=Name

controls the name sent to the

Historian Server in order to establish the PI API trust. Prior to
version 4.1 of UniInt, the interface name was used to establish
the PI API trust with the Historian Server. This limited the
Historian

Administrator‟s options when setting up security for

an interface node. There was no way to configure different PI
API trusts for different instances of the interface running on
the same computer. The Historian Administrator is now able to
specify an application name for each instance by using the

/AppName=Name

parameter.

The maximum length of the

Name

is 4 characters. Please

keep in mind when setting up the Trust that the PI API puts an
E at the end of the application name.

The Application Name that is sent to the Historian Server can
be viewed in the Historian Server Message Log immediately
after an interface is started. A message will be written to the
message log stating the connection status for a “process
name”. The “process name” is the application name sent from
the interface.

/dbUniInt=level

Optional

Defualt = 0

The

/dbUniInt

parameter is used to set a debug level for

debugging UniInt code.

level

is a 32-bit integer. Setting a

particular bit in

level

to 1 turns on a particular debug

switch. To turn on every debug switch specify:

/dbUniInt=0xFFFF

level

can be specified as either a decimal number or a

hexadecimal number. A

0x

must precede hexadecimal

numbers.

The following table lists the sections of code that can provide
debug information and the hexadecimal value that

level

must equal in order for that section to output messages.
Multiple sections can output debug messages simultaneously
by adding the values together. For example, both initiailization
and shutdown can be debugged by adding the two

level

Values 0x02 and 0x08 together and specifying

level

as

0x0A.

UniInt Area

Hexadecimal Value

Initialization

0x0002

Shutdown

0x0008

Saving to Historian

0x0010

Control Loop Function

0x0020